HomeMy WebLinkAboutILIAMNA ACRES TR 4AIliamna Acres Tract 4A #017-101-22 (Kev Ub/U2/16) Municipality of Anchorage On-Site Water and Wastewater Section • (907) 343-7904 f, of 3 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP201330 PID Number: 017-101-22 "OZ, Dwelling: 9 Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New X Upgrade Name Ted & Leslie Kramer ABSORPTION FIELD El Deep Trench XWide Trench El Bed ❑Mound Site Address 5400 E. 142nd Avenue Anchorage, AK 99516 ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 985-867-0665 1 5 1.0 GPD/SF +2.25 / +0.95 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade +2.75 / +1.40 Ft. Gravel depth beneath pipe .5/.45 Ft. Subdivision Block Lot Iliamna Acres Tract 4A Fill added above original grade 5.45/3.95 Ft. Gravel length 75/75 Ft. Township Range Section Gravel width 5 Ft. Beds: Number of Lines Distance between lines Ft. SEPARATION DISTANCES To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line 750 Ft2 2 > 6 Ft. Well >100' >100' N/A N/A >25' TANK 0 Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Capacity Greer 1,500 Gal. Surface Water >1 >1 00' N/A N/A Material Number of compartments Lot Line >5' >10' N/A N/A NA Plastic 2 Foundation >10' >10' N/A N/A LIFT STATION Manufacturer N/A Capacity Gal. Remarks 2" Insulation over absorption trenches. Alarm location Electrical installed by PIPE MATERIAL House to tank D3034Tank to D3034 drainfield Installer Denali Excavation Drainfield D3034 CO/MT D3034 Inspector J. Millette / L. Tidwell BENCH MARK (Assumed elevation) 100 ft Inspection151 10/12/20 10/14/20 Location and description 3rd 4,h Bottom of Siding at S.E. Corner. ON-SITE WATER AND WASTEWATER SECTION APPROVAL Engineer's Stamp ®� ®OFq� ®�+e Conditional Approval: Date ®�®P.•••'""""••:qS �4. Aw • 49th ® ............. I.................................. E. ANDERSON• g= W Septic System �i AW ®s No. CE-4381 ,' �� ��'F'°••.., Approved ( Date 1/1 1 402 6/18/21 •.••°'C�=�® ♦e Note: this approval does not include well permit requirements. a�®��®®®S®®®�®®®®® (Kev Ub/U2/16) // // // ALTERNATE SITE: CATEGORY III SYSTEM w/30' LONG x 5' WIDE x .5' EFFECTIVE DEPTH ABSORPTION TRENCH. APP. RATE 5 GPD/SF. 1"=50' 2-75' LONG x 5' WIDE x .5' EFFECTIVE DEPTH ABSORPTION TRENCHES CO - CLEANOUT 2CO - DOUBLE CLEANOUT FCO - FOUNDATION CLEANOUT FS - FLOW SPLITTER VALVE MH - MANHOLE MT - MONITORING TUBE SV - SEPTIC VENT TH - TEST HOLE LEGEND TH2 PERMIT # OSP201330 PID # 017-101-22 ILIAMNA ACRES SUB, TRACT 4A A B MH1 69.2 SV1 73.4 A B 2CO2 78.8 CO1 105.7 MT1 107.5 MT2 136.5 47.5 49.8 54.6 77.85 79.5 115.05 EAST 142 AVE FEET 0 50 100 GARAGE 10' UTILITY EASEMENT SHED TH1 5 7 5 570 565 EXISTING WELL THREE BEDROOM HOME TOE OF FILL SLOPE CO4 MT6 CO3 CO1 CO2 MT4 MT3 MT1 MT2TOE OF FILL SLOPE 1,500 GALLON SEPTIC TANK w/20" MANWAY. 2CO2 SV1 MH1 ALTERNATE SITE TOE OF SLOPE. TOTAL HEIGHTS 2.5' ABOVE GRADE. 2' SEPARATION TO GROUNDWATER, 3' TO IMPERMEABLE LAYER. FENCE. NO WELL OR SEPTIC CO2 141.9 MT3 143.3 CO3 130.1 MT4 128.1 MT5 153.2 C04 156.1 MT6 154.6 127.75 128.8 97.0 95.5 130.5 137.2 135.7 MT5 PLAN AS-BUILT FS PT3 2CO1 2CO1 28.939.0 ABANDONED TRENCH 6/18/21 PROFILE AS-BUILT (NO SCALE) 82.55 76.9 83.1 89.4MH SV1500 GAL SEPTIC TANK 2CO282.3 PERMIT # OSP201330 PID # 017-101-22 ILIAMNA ACRES SUB, TRACT 4A 7/8/212CO1 PROFILE AS-BUILT (NO SCALE) 75' 81.85 FINISH GRADEMT1 TH#272.4 GROUNDWATER MONITORING 10/12/20 79.15 CO1CO270.4 78.65 76.4 ORIGINAL GRADE MT3MOA APPROVED SAND LINER DRAINFIELD ROCK 75' 77.3 FINISH GRADEMT4 TH#269.35 GROUND WATER MONITORING 10/12/20 74.374.75 CO3CO467.35 74.3 74.75 73.35 ORIGINAL GRADE MT6MOA APPROVED SAND LINER DRAINFIELD ROCK 71.5571.55 74.4 78.65 79.15 75.1 PERMIT # OSP201330 PID # 017-101-22 ILIAMNA ACRES SUB, TRACT 4A 8/10/21MT2MT578.65 74.3 LEGAL DESCRIPTION: PERFORMED FOR: DATE: PARCEL ID#: SOILS LOG AND PERCOLATION TEST TECHNICIAN: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DEPTH (feet) PROJECT No.: TEST HOLE 2 SLOPE SLOPE SITE PLAN DATE READING GROSS TIME(minutes)NET TIME(minutes) DEPTH ofWATER NET DROP PERC. HOLE DIA. (INCHES)PERCOLATION RATE: (MIN/INCH) TEST RUN BETWEEN: FT. and FT. COMMENTS: (inches)(inches) ILIAMNA ACRES SUB TR-4A 7/31/20 M. Jakubisin DATE OF MONITORING: WAS GROUND WATER ENCOUNTERED? DEPTH TO WATER AFTER MONITORING: IF YES @ WHAT DEPTH?- 1.1 6 3 4 017-101-22 TED KRAMER 12:38/12:43 8/3/20 1 2 3 6"/0 12:45/12:52 12:55/1:02 1' OB Professional Engineers Stamp: 5:20 NO 4.5 8/10/20 GM BOH HARD PAN 6" 6"/06:55 6" 6"/07:01 6" Measurements taken to 1/16". Percolation test will be redone and verified prior to construction. 7/8/21 6.0 10/12/20 LEGAL DESCRIPTION: PERFORMED FOR: DATE: PARCEL ID#: SOILS LOG AND PERCOLATION TEST TECHNICIAN: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DEPTH (feet) PROJECT No.: PERK TEST 3 SLOPE SLOPE SITE PLAN DATE READING GROSS TIME(minutes)NET TIME(minutes) DEPTH ofWATER NET DROP PERC. HOLE DIA. (INCHES)PERCOLATION RATE: (MIN/INCH) TEST RUN BETWEEN: FT. and FT. COMMENTS: (inches)(inches) ILIAMNA ACRES SUB TR-4A 5/14/21 J. MILLETTE DATE OF MONITORING: WAS GROUND WATER ENCOUNTERED? DEPTH TO WATER AFTER MONITORING: IF YES @ WHAT DEPTH? 3.0 6 2 3 017-101-22 TED KRAMER 12:45 5/14/21 1 2 3 6 0 16 / 9 8 16 12:56 1:08 Professional Engineers Stamp: 10 3 8 16 10 10 1:204 5 6 1:31 1:42 10 10 10 6 0 16 / 9 7 16 3 7 16 6 0 16 / 9 6 16 3 6 16 6 0 16 / 9 5 16 3 5 16 6 0 16 / 9 5 16 3 5 16 6 0 16 / 9 5 16 3 5 16 6/18/21 MUNICIPALITY OF ANCHORAGE On -Site Water & Wastewater Program PO Box 196650 4700 Elmore Road Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997 http://www.muni.org/onsite On -Site Wastewater Disposal System Permit Permit Number: OSP201330 Work Type: Septic Upgrade Tax Code Number: 01710122000 Site Legal Address: ILIAMNA ACRES TR 4A G:3037 Site Mailing Address: 5400 E 142ND AVE, Anchorage Owner: KRAMER TED E & LESLIE J Design Engineer: FORGE ENGINEERING This permit is for the construction of: Effective Date Expiration Date Lot Size in Sq Ft: Total Bedrooms: I r t�C'I)al'TI]INnT 8/26/2020 8/26/2021 99274 0 Disposal Field 0 Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80) 3. The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to prevent freezing Special Provisions: The Engineer is required to do an additional percolation test prior to construction of the septic field. Percolation tests are to be performed according to the Wastewater code. Please submit stamped and signed results with the As -built Inspection Report. If the results require a design change, construction of the system will stop pending On -Site review and approval. Received By: Issued By: Date: Date: 5 MUNICIPALITY OF ANCHORAGO Community Development Department = q Phone: 907-343-7904 Development Services Division Fax: 907-343-7997 On -Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION Parcel I.D. 017-101-22 Property owner(s) Ted & Leslie Kramer Mailing address 5400 E. 142nd Avenue Anchorage, AK 99516 Site address Same Day phone 985-867-0665 Legal description (Sub'd., Block & Lot) Iliamna Acres, Tract 4A Legal description (Township, Range & Section) Lot Size 99274 Sq. Ft. Number of Bedrooms Five (5) APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (® all that apply) Absorption Field ❑X Initial ❑ Single Family (SF) ❑X (w/wo ADU) Septic Tank 7X Upgrade ❑X Duplex ❑ (D) Holding Tank ❑ Renewal ❑ Multiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit/Rush Fees4 q`7 6- o 5 (Uv i D-1 � Date of Payment: 2 0/.2- 02 v Receipt Number: Q`16 3 - Permit Permit No. 0 5 A 20.1 3 3 0 Permit App_'- :- : ..:c iver Fees: Date of Payment: Receipt Number: Waiver No. PO BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 (FAX) August 19, 2020 M.O.A. Development Services Department On-Site Water & Wastewater Program 4700 Elmore Road Anchorage, AK 99507 Subject: Iliamna Acres, Tract 4 – 5400 East 142nd Avenue Septic System Design Dear On-Site Services Engineer: The existing septic system on the subject lot has failed and must be replaced to serve the three- bedroom home on the property. The new septic system is designed to serve a five-bedroom home at the request of the owner. We are submitting this permit application for the construction of a new septic system. The attached site plan identifies the location of the home and the existing well and the existing and proposed septic system. No conflicts exist between this proposed system and any other well or septic system on this lot or adjacent lots. The ground surface on the lot slopes to the west at grades approximating 15%. There are no slopes greater than 25% within 50 feet downslope of the proposed site. Ground contours are shown on the site plan indicating the grade and direction of flow. Stormwater drainage will not impact this septic system. The new trenches will be constructed parallel to the slope as much as possible. Wells on this and adjacent lots are shown. The new system will be a minimum of 100’ from all wells and surface water and more than 5’ from the septic tank. Please refer to the attached test hole log and plan and profile sheets for the septic design. If this design is followed, there will be no adverse impacts to adjacent properties. Sincerely, Michael E. Anderson, PE 8/19/20 Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP201330, Deb Wockenfuss, 08/26/20 // // //ALTERNATE SITE: CATEGORY III SYSTEM w/30' LONG x 5' WIDE x .5' EFFECTIVE DEPTH ABSORPTION TRENCH. APP. RATE 5 GPD/SF. 1"=50' 2-75' LONG x 5' WIDE x .5' EFFECTIVE DEPTH ABSORPTION TRENCHES NOTE: NO SLOPES >25% WITHIN 50' OR SURFACE WATER WITHIN 100' OF THE PROPOSED SEPTIC SYSTEM ALL WELLS ON SURROUNDING LOTS WITH IMPACTS TO THIS PROPERTY ARE SHOWN. NO CONFLICTS WITH WELLS OR SEPTIC SYSTEMS. CO - CLEANOUT 2CO - DOUBLE CLEANOUT FCO - FOUNDATION CLEANOUT FS - FLOW SPLITTER VALVE MH - MANHOLE MT - MONITORING TUBE SV - SEPTIC VENT TH - TEST HOLE LEGEND TH1 ILIAMNA ACRES, TRACT 4A EAST 142 AVE 8/26/20 FEET 0 50 100 GARAGE 10' UTILITY EASEMENT SHED TH2 57 5 570 565 EXISTING WELL THREE BEDROOM HOME TOE OF FILL SLOPE CO MT CO CO CO MT MT MT MT DECOMMISSION EXISTING SEPTIC TANKS PER U.B.C. ABANDON EXISTING ABSORPTION TRENCH. TOE OF FILL SLOPE 1,500 GALLON SEPTIC TANK w/20" MANWAY. 2CO SV MH 2CO FS ALTERNATE SITE TOE OF SLOPE. TOTAL HEIGHTS 2.5' ABOVE GRADE. 2' SEPARATION TO GROUNDWATER, 3' TO IMPERMEABLE LAYER. FENCE. NO WELL OR SEPTIC Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP201330, Deb Wockenfuss, 08/26/20 ILIAMNA ACRES, TRACT 4A DESIGN FACTORS: SYSTEM REQUIREMENTS: 750 GPD PEAK FLOW PERK RATE: 1-5 MIN/IN APPLICATION RATE: 1.0 GPD/SF 5' WIDE TRENCH SYSTEM 1,500-GALLON SEPTIC TANK TYPICAL TRENCH SECTION (NO SCALE) 4" PERFORATED PVC (HOLES DOWN) DRAINFIELD ROCK 5' 6" 2' 6" NOTES: 1. GRADE AREA OVER TRENCH TO DRAIN AWAY 2. PROVIDE 3' OF COVER OVER TRENCHES AND 4' OVER SEPTIC TANK, OR 2' WITH 2" OF INSULATION 3. CHECK GROUNDWATER AT TIME OF CONSTRUCTION. IF LEVEL IS HIGHER THAN PREVIOUSLY OBSERVED, CALL ENGINEER IMMEDIATELY BOTTOM OF TRENCH: 1.5' ABOVE GRADE FLOW LINE ELEVATION: 2.0' ABOVE GRADE TOP OF TRENCH: 4.0' ABOVE GRADE 750 GPD / 1.0 GPD/SF /5' WIDE - 1.0 (RED. FACTOR) = 150 LF TRENCH REQUIRED (150 LF SPECIFIED) 8/19/20 2.5' MOA APPROVED SAND 2" INSULATION & GEOTEXTILE FABRIC 1.5' REMOVE ORGANIC MATERIAL TO UNDERLYING RECEIVING SOIL (GM). REPLACE WITH MOA APPROVED SAND. NOTE: 6" TOPSOIL & REVEGETATE MOUND. 3 1 3 1 Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP201330, Deb Wockenfuss, 08/26/20 LEGAL DESCRIPTION: PERFORMED FOR: DATE: PARCEL ID#: SOILS LOG AND PERCOLATION TEST TECHNICIAN: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DEPTH (feet) PROJECT No.: TEST HOLE 2 SLOPE SLOPE SITE PLAN DATE READING GROSS TIME (minutes) NET TIME (minutes) DEPTH of WATER NET DROP PERC. HOLE DIA. (INCHES)PERCOLATION RATE: (MIN/INCH) TEST RUN BETWEEN: FT. and FT. COMMENTS: (inches)(inches) ILIAMNA ACRES TR-4A 7/31/20 M. Jakubisin DATE OF MONITORING: WAS GROUND WATER ENCOUNTERED? DEPTH TO WATER AFTER MONITORING: IF YES @ WHAT DEPTH? - 3.2 6 3 4 017-101-22 TED KRAMER 11:50/12:00 8/3/20 1 2 3 4 6"/0 12:04/12:20 12:20/12:39 12:46/1:05 1' OB Professional Engineers Stamp: 8/19/20 10:32 NO 7.0 8/10/20 GM BOH HARD PAN 6" 6"/016:10 6" 6"/019:35 6" 6"/019:41 6" Measurements taken to 1/16". Percolation test will be redone and verified prior to construction. Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP201330, Deb Wockenfuss, 08/26/20 LEGAL DESCRIPTION: PERFORMED FOR: DATE: PARCEL ID#: SOILS LOG AND PERCOLATION TEST TECHNICIAN: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DEPTH (feet) PROJECT No.: TEST HOLE 2 SLOPE SLOPE SITE PLAN DATE READING GROSS TIME (minutes) NET TIME (minutes) DEPTH of WATER NET DROP PERC. HOLE DIA. (INCHES)PERCOLATION RATE: (MIN/INCH) TEST RUN BETWEEN: FT. and FT. COMMENTS: (inches)(inches) ILIAMNA ACRES TR-4A 7/31/20 M. Jakubisin DATE OF MONITORING: WAS GROUND WATER ENCOUNTERED? DEPTH TO WATER AFTER MONITORING: IF YES @ WHAT DEPTH? - 3.2 6 3 4 017-101-22 TED KRAMER 12:38/12:43 8/3/20 1 2 3 6"/0 12:45/12:52 12:55/1:02 1' OB Professional Engineers Stamp: 8/19/20 5:20 NO 4.5 8/10/20 GM BOH HARD PAN 6" 6"/06:55 6" 6"/07:01 6" Measurements taken to 1/16". Percolation test will be redone and verified prior to construction. Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP201330, Deb Wockenfuss, 08/26/20 CS1 0i Lwu- - - - - - - - - - - - - - - -- - - - - S i 10' Ilya ESur N 0' 06'00"W r sn Il Es-------X00$3'— -------- I I g CJC mx--iamN iJ I crni»y m A C I zc>Scn- I Iornc= I I c ymCA c I P IoaojP ymiNC Nr yzn n-I zOSZANr-n2 I I CS1 0i Lwu- - - - - - - - - - - - - - - -- - - - - S i 10' Ilya ESur N 0' 06'00"W r sn Il Es-------X00$3'— -------- I I g I a O V E I I I I I I I CEJ I I N 90 V 5 CJ+ c.+ N Z OSN mO NO-I fTI N.- mO N OZ7 Zl N N C m r mil 00 '- oa f*l CDn -G N F1 C M - i C)Z O5 C-=im I O I M:n u O VDiD ND mC> O W 50O fin' m X Sm D N ZE a C=N C CDn U5 CT) N CD rEi O --< rC< OC O xC~Af TI czi Zp O( n co vCp cmi cn O oT z=r Dcnc OC5 DNZO - EDD O n OJ Z C ~ =-< Mm GJ O n m m Cn fTl p (n O C z C M C) oCDS -' gym o I D C->C r W y CO Z Z =Z DO rte= N z O D m O r;;, O m p_ -o a a oHm c -a vz A a D Oo.Z7 0 0 C C oom w 70m O~ co m C'" n a S Z V O m C z w N z C = 0p p W Z O G mZ7C7 O Z-, 5 HOZ _ Cn E EE aj W NO NO CJC mx--iamN iJ I crni» y m A C ooaz -imN 00. 0 O% n% oArnno m+ioZ I o z o sczn IQ m S- zmnAmm-y cn czWoomf- P p ymiNC Nr yzn n-I zOSZANr-n2 I zc Arni i I I a O V E I I I I I I I CEJ I I N 90 V 5 CJ+ c.+ N Z OSN mO NO- I fTI N.- mO N OZ7 Zl N N C m r mil 00 '- oa f*l CDn -G N F1 C M - i C)Z O5 C-= im I O I M: n u O VDiD ND mC> O W 50O fin' m X Sm D N ZE a C= N C CDn U5 CT) N CD rEi O --< rC< OC O xC~Af TI czi Zp O( n co vCp cmi cn O oT z=r Dcnc OC5 DNZO - EDD O n OJ Z C ~ =-< M m GJ O n m m Cn fTl p (n O C z C M C) oCDS -' gym o I D C->C r W y CO Z Z =Z DO rte= N z O D m O r;;, O m p_ -o a a oHm c -a vz A a D Oo.Z7 0 0 C C oom w 70m O~ co m C'" n a S Z V O m C z w N z C = 0p p W Z O G mZ7C7 O Z-, 5 HOZ _ Cn E EE aj W NO NO 00. 0 O% n% yo a _i o Development Services Department Building Safety Division *A1 On-Site Water & Wastewater Program4700 Elmore RoadP.O. Box 196650 `Mark Begich Anchorage, AK 99507 Mayor www muni.om/onsite (907)343-7904 Pump Installation Log Well Drilling Permit Number: SW Date of Issue: Parcel Identification Number: Legal Description Property,Owner Name & Address:_ �La WL n a /_EStiE � %ED KRAmoe �R Si(OaC, gzwA-4c i[o-zloaz Pump Installation Date: Pump Intake Depth Below Top of Well Casing: qd feyet�/fe��x�(y� Pump. Manufacturer's Name: Pump Model: '7V Pump Size JV2, hp Pitless Adapter Burial Depth: / V feet Pitless Adapter Manufacturer's Name: Pitless Adapter Installer: A))4 - Well Disinfected Upon Completion? Wes ❑ No Method of Disinfection: 4 ,o z Comments: Pump Installer Name: �T�/ 3 ANCHORAGE WELL & PUMP SERV. 0111112 330 EAST 76TH AVENUE ANCHORAGE, AK 99518 AWPS.COM PHONE: 907-243-0740  MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEAl_TH & ENVIRONMENTAL PROTECTION ENVIRONMENI'AL ENGINEERING DIVISION 825 L Street - Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT NA TPHONE. LOCATION · dSq q <J,g Ma n u f act u rer ,~ r,,,~___. ~. ¢/~ gallons IF HOMEMADE: Well DISTANCE TO: Inside !e n gt h~_...~_=_.~ DISTANCE TO: No. of lines [ Length of each F°undati°n 7,~ 0 ~ Material Tota engt~ of nes~y~ Tronch width~-~'' ~J inches NO, OF BEDROOMS PE Dq9 No. of cl~.~tmeats Liquid depth PERMIT NO. a of tile to finish grade Material beneatl] tile Length Width Depth Type of crib ;rib depth Well DISTANCE TO: Depth foundation Nearest Io:t~) ~. DISTANCE TO: Total effecl lot line Distance between lines inches · ption area )tion area Building founda D riller.~..~_ Distance to Sewer line PERMITNO' 7¢ Absorption OTHER A 'PF~V E D .(~ DATE 72-013 (Rev. 3/78) Glr "~.TER ANCHORAGE AREA BOROF '~H HEALTH DEPARTMENT 327 EAGLE ST. ANCHORAGE, ALASKA 99501 279-2511 N? g33 INSPECTION REPORT ON-SITE SEWAGE DISPOSAL SYSTEM LOCATION SEPTIC TANK: °,STANCE FRO,,,, WELL / ZO" LIQUID CAPACITY /~ '~9 ¢ NUMBER OF INSIDE LENGTH INSIDE WIDTH .GALLONS. MAILING ADDRESS IIZ LIQUID _DEPTH SEEPAGE SYSTEM: SEEPAGE PIT: NUMBER OF PITS / OUTSIDE DIAMETER L,N,NGMATER,A, . NEARESi' LOT LINE ! / DISTANCE FROM WELL / ~ 0 l __ , BUILDING FOUNDATION TOTAL EFFECTIVE ABSORPTION AREA (WALL AREA) '~ (~' SQ. FT. TILE DRAIN FIELD: TOTAL LENGTH DIS,~E-.F~R~.~ WELL ,-~-%, ,FOUNDATION ,NEAREST LOT LI~ ,O~ . (/ABSORPTION AREA SQ. FT. LENGTH OF EACH LINE~'~ DEPTH: TOP OF TILE TO FINISH GRADE DEPTH OF FILTER MATERIAL BENEATH TILE IN. ABOVE TILE__ WELL: TYPE. L{¢;//~ DEPTH. ~Z j DISTANCE FROM "'~ ~ WATER ,BUILDING FOUNDATION, SAMPLE ., NEAREST '.J__ NEAREST SEPTIC ' ~ ~ 12~' SEEPAGE /~ OTHER / T , SEWER LINE , TANK - , SYSTEM , CESSPOOL .... , SOURCES LOT LINE DISTANCES: ,4,-C z: I ZOI / 'A ,4// DIAGRAM OF SYSTEM C' DATE HEALTH AUIHORIIY 1"1'11~ t..l:::l'.,It..:iTH I:::,;[ I"'ll:if:l",l:!ii;): 01",! :!: '.:~:; "J't'll:1{ I...l:i~:l",l(':i-I"H ( '_1: Iq I':'l:!!:lii2F ::, OF:' 't'l..'h~:: 'I:'f;i:I::~:NE:I.I l:':ll:~: I';:,Fi:I:::I :i: i'.,ff::' :[ El .D. l:'~l~i:: DEI::'TH CII::' I:::1 "I'I';i~E~NC:H Ell:ii'. I:::'1"1" ii7::i:; "1'1.1[~i D)::~i;TI'::II'.,IC[iil Ediii'l'l,.ll::i[~:l'.,l THE' :ii;l:.tl:~:l::;'F:l('i:l:il 01= 'Tl'ff~i GF.'.'OI:..II'.,tt;} F'II'.,I[.:, 'l:'l:ll:iil E:CII'TCtP1 C'll:= 'T'HEi f!i'.',:.OZ:I::I',,,'FIT]it:.iIt'.~ ,:ill:lq '-ii' Ir'"'l:t L: :.. "'~F' IF:~ lEE: Ii'"',,~ ~:Z::: ~"' '~ I..1.ql :1[' IE:::,~ '"IF' Ii'-'l~ 'ii' ."ii!~; ~ IF::::" IE:!i: I!!iiiii: -ii" :ir: r'l , r:: t.. [::'l:~:l:::q-H :1: !i!: 'I"HE I:'I :~: i",l .[ I'"ll..li'"l I::'~::I:="I"H I:::tl::' GI:,i~I'::t',/~:I.. FIN(::' 'THI:{ [}i;i:::Fl:'T(:ll:,'l 01':: 'I"HE I:ii:::'::E:F:I',,,'F:I'I":I:I::)BI '::J:t",l [:'E-i!ET::,. : :' l!!!: l:~i', i'"l :l: 'T I::'IF'F:'L.):I:::FfI",I'I" I'll:i:ii: 'I'HI'ii: [,.:L:!'.!:i;l:x'Ol",l:ii!;:(l~!:]:l..~:l:'t"-r' TO :l:BIl::'l:::ll:~::l"t l'l't:(:ii; [::'l':i:Pl':ll;i'.Ti'"l[i:l",l'l:' [::,I..IB:]:NI::!i TI'Il:ii: :i:I",I:!!!:TI:::iI.I..I:::I-I:']:ON ):N::iiil::'EC:T:[EIf',l:ii; 01:= t:::!N"r' .t,.ll'i:L.L..!!il t:'l[::'..:rl:::lC:l:ii:Nl' '1"O TI"I):~!!; I:::'[;;:CIF'I::::Fi:'I"T' F:INI:::' THE: Iql_.il"ll:i:liii:l:ill CIF:' Fi:l:ii:!:il]:[::'[!{i",lE:l:ii::i~i "['HFIT THE: I.,I:I:!!:L.I... I.,.I:I:L.I... Fi',f:lC:k:f; :i: I..I .. :[ b,l(:Fi OF:' l:::lt",l~'r' '.i'];"r"_::;'FEl:'l H :i: TI'IOI...IT F:' .1:. I",ff::l[. :[ I",I:i:~;F'[CI:::T :i: ()N F:II",II::~ I:::II:':'F'I:;i:(')',,,~I:t:IL. [ii¢'r' TI'I :i: :B [::'li!i:l:::'i:::ll:;i:TH[!!:t'q'l* I.,.l:[t..I.. [ii',[~: :E;I:.II:~L]'[!i:C:T TO August 14, 1979 Don Bender Box 68 Talkeetna, Alaska Subject: Tract 4A Illiamna Acres Overflowing Sewage Complaint ~791542 Dear Mr. Bender: The on-site sewer system on your lot has failed and an upgrade is required. If the house is not in use, this department has no objection to delaying the upgrade. However, prior to occupancy, an upgrade is required. You indicated that the present tenants will be vacating the house by September 1, 1979. It is your responsibility to keep the sewage off the ground even if it requires daily pumping. It will be your responsibili~y to inform this department when the house is vacated, and when occupancy is resumed. This department will make periodical checks during the period of vacancy for overflow. If there are any further questions, please contact this off,ce at 264-4720. Sincerely, Lynn Lindquist Senior Environmental Code Officer LL/ljw cc: Ken Norman Legal Department GAAB-I-I D-2 GREATER 327 Eagle St. XNCHORAGE AREA I ')ROUGH CaseSo.//: HEALTH DEPARTMENT Anchorage, Alaska 99501 279-2511 / SEWAGE DISPOSAL SYSTEM - APPLICATION & PERMIT RES,.ENCE A.D.ESS .~o.~___- LOCAT,ON DF ,NSTALL^T.ONI~afSX'~-~ ~ ~ff,'?k~ LEGAL DESCRIPTION SEEPAGE PIT ., DRAIN FIELD , OTHER ~ D p.r~ 'TT a ~ ~. ak TO ,~E ,NSTAL.E..Y_ . ANTICIPATED DATE OF COMPLETION APPLICATION TO INSTALL: SEPTIC TANK TO SERVE THE FOLLOWING FACILITY FINANCED T.R0UaN ~e. C ~ PERCOLATION TEST RESULTS BELOW TO BE FILLED OUT BY HEALTH DEPARTMENT T.IS .S TO SE.YE AS ?Y~' /~ AS DESCRIBED BELOW. . SEPTIC TANK SIZE DISTANCES: , PERMIT TO INSTALL A SIZE OF UNIT T0 BE SERVED TYPE (~Q/Tt&~/~-EPAGE AREA TYPE HEALTH AUTHORITY OR LICENSED DESD~NER I certify tha. t I am fa,nil!ar, with the 'requir.emen!s of Greater Anchorage A,~eaz B°r°tlgb9,, rd~ance Ngd~8-S~'and. that,__ above descnbe~ systen~ ,s in accordance with said code. ~.~ff~/f(.~.c/~,_L// DATE ~ APPLICANTSSIGNATUR ~ ¢//~ ~ MUNICIPALITY OF ANCHORAGE Development Services Department Phone: 907-343-7904 On -Site Water & Wastewater Section Fax: 907-343-7997 Certificate of On -Site Systems Approval Parcel I.D. 017-101-22 Legal description Illamna Acres Tract 4A Site address 5400 E 142nd Ave, Anchorage Current property owner(s) Kramer Expiration Date: 1-18-2023 X The On-site system(s) is/are approved for 5 bedrooms Conditional approval for Comments or advisories: bedrooms, with the following stipulations: � JJ By: Original Certificate Date: This Certificate of On -Site Systems Approval (COSA) is intended to demonstrate the subject system(s) is/are in substantial compliance with municipal code. The Municipality of Anchorage, Development Services Department (DSD) issues COSAs based upon representations provided by an independent professional engineer. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. ATTACHMENTS: COSA Checklist X Well Flow Advisory Absorption Field Advisory Nitrate Advisory x Tank Age Advisory Arsenic Advisory Other COSA Approvdjune 2022 MUNICIPALITY OF ANCHORAGE ii Development Services DepartmentNa�)7 Phone: 907-343-7904 On -Site Water & Wastewater Section Fax: 907-343-7997 Certificate of On -Site Systems Approval Application 1. GENERAL INFORMATION Parcel 1. D. 017-101-22 Complete legal description Iliamna Acres, Tract 4A Location (site address) 5400 E 142nd Avenue, Anchorage, AK 99516 Current property owners) Ted & Leslie Kramer 2. ON-SITE SYSTEMS SIZED FOR 5 BEDROOMS Day phone (907) 350-1221 3. TYPE OF WATER SUPPLY: ❑■ Private Well ❑ Private Well serving 2 dwelling units ❑ Private Well serving 3+ dwelling units ❑ Community Well or Public ❑ Water Storage 4. TYPE OF WASTEWATER DISPOSAL: ❑■ Private Septic ❑ Private Septic serving 2 dwelling units ❑ Holding Tank ❑ Community Septic or Public Sewer 5. SEPTIC TANK: ❑ Steel ❑■ Plastic ❑ Concrete ❑ Fiberglass Age <2 - See advisory if steel older than 20 years 6. ABSORPTION FIELD: ❑ AWWTS ❑ Bed ❑ Deep Trench ❑■ Wide Trench ❑ Seepage Pit Waiver request for: Expedited review requested: ❑ Distance: By applying for this entitlement, this property is subject to inspection by municipal On-site staff to verify the accuracy of the information provided. COSA Fee $ ai ?0 Date of Payment /U z7- f2� COSA # 'a UO�lS�D Waiver Fee $ Date of Payment Waiver # COSA Application—June 2022 COSA Checklist Legal Description: Iliamna Acres,Tract 4A Parcel ID: 017-101-22 If more than 1 well and/or septic system on lot, provide separate checklist. Structure served by this system _ A. WELL DATA ❑ Well log is filed with Onsite (or attached) Date drilled -- Total depth 98* ft Cased to 50+* ft ❑ Sanitary seal is functioning correctly ❑ Wires are properly protected Casing height (above ground) 26 in. Date of flow test for COSA 9/26/22 Static water level at beginning of test 22 ft. Comments *Per inspection 8/2/12 B. TANK DATA Measured operating fluid level in septic tank NEW Date of pumping 10/7/22 Northland Pumping ❑ Required maintenance completed, if AWWTS Comments: D. ABSORPTION FIELD DATA Which system tested (date installed) 10/12/22 ❑ ALL standpipes present per record drawing Total measured depth from grade 3.2/3.0 ft (max) Measured depth to pipe invert from grade 2.7/2.55 ft (min) ❑ N/A — pressurized field. ❑ Per record drawings, field is insulated. ❑ Monitor tubes go to bottom of effective. If not, state depth into effective ❑ Presoaked required if (Required if house vacant or field not used for more than 30 days prior to date of test) Gallons introduced N/A gallons N/A date Any rejuvenation treatment (past 12 months) N/A If yes, enter date Comments/Deficiencies: COSA Checklist June 2022 Well production at time of test 3.6 gpm Water storage tank volume gallons Well disinfected for coliform test? ❑ Yes ❑ No ❑ Coliform bacteria is Negative Nitrate 6.35 mg/L ❑ Nitrate less than MRL (ND) Arsenic ug/L ❑ Arsenic less than MRL (ND) Collected by Forge Engineering Date 9/26/22 C. LIFT STATION fired maintenance completed Age of lift station years Lift station material Comments: Adequacy test date NEW Results ❑ Pass Nid depth prior to test in Wat added gal New flui depth in Elapsed tim6\ min Final fluid depth_ in Absorption rate > gpd FIELD STATUS — POS ECOVERY Effective depth (per recor\aw,) in Effective depth used Effective depth remaining E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well on lot) Septic Tank/Lift Station on Lot > 100' Community Sewer Manhole/Cleanout > 100' Fm]Yes if No ft QQ Yes if No ft Neighboring Tank > 100' g Yes if No ft Private Sewer/Septic Line > 25' ❑® Yes if No ft Absorption Field on Lot > 100' M Yes if No ft Holding Tank > 100' Mm Yes if No ft Neighboring Absorption Fields > 100' Animal Containment > 50' Yes if No ft 0 Yes if No ft Manure/Animal Excreta Storage > 100' Community Sewer Main > 75' Yes if No ft ❑ Yes if No ft ❑ N/A — Served by Community Well (not on lot) or Public Water From Septic/Holding Tank and Absorption Field(s) on Lot to: (Please enter distances if less than required) Building Foundations > 10' Fm_1 Yes if No ft Surface Water > 100' M Yes if No ft Tank to Property Line > 5' 0 Yes if No ft Wells on Adjacent Lots: Field to Property Line > 10' [E Yes if No ft Private Wells > 100' 0 Yes if No ft Water Main > 10' FE] Yes if No ft Community Wells > 200' Fm] Yes if No ft Water Service Line > 10' FEI Yes if No ft If tank or field is under driveway comment below F. ENGINEER'S COMMENTS G. CERTIFICATION & STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines, indicates that the on-site water supply and/or wastewater disposal system appears to comply with applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation, unless noted otherwise. Name of Firm Forge Engineering Engineer's Printed Name Benjamin Schiller, P.E. COSA Checklist—June 2022 Phone (907) 522-7773 Date 9/28/22 4� TM _ Benjarri S'chiller CE 12592cv`4`�® AW ���kFAF�pROFESSO��.� Nitrate Advisory Certificate of On -Site Systems Approval # OSC 221496 Subdivision: Iliamna Acres Tract 4A A water sample revealed a nitrate concentration of 6.35 milligrams per liter (mg/Q. The Environmental Protection Agency (EPA) has established a maximum contaminant level (MCL) of 10.0 mg/L for public drinking water systems. While private wells are not subject to this regulation, EPA standards are based on existing health information and can therefore be used to gauge the relative quality of water from private wells. Please see the attached "Nitrate Fact Sheet" for important information regarding nitrate. This advisory must be attached to all copies of the subject Certificate of On -Site Systems Approval. MaiUng Address P O Box 196650 *Anchorage, Alaska 99519 6650 *www muni org From Northern Testing Laboratories, Inc. Nitrate is a negatively charged compound of nitrogen and oxygen, which is very soluble in water. Nitrate is not readily filtered or otherwise removed in the soil and can pass rapidly into ground water wells. SOURCE: Nitrate is a major component of fertilizer and wastewater. Often the nitrate is in the form of ammonia or protein first, which through contact with oxygen and certain bacteria, converts to the oxidized form known as nitrate. Sources of nitrate from wastewater include urea, ammonia cleaners, food solids, and bacterial cells. It may also result from the breakdown of organic matter buried in the soil. TOXICITY: Nitrate is generally not toxic to adults or children over the age of two or three years but is associated with a potentially fatal infant disease called methemoglobinemia. In the digestive system of young children, nitrate converts to nitrite, which can pass through the intestinal wall into the blood stream. There it combines with the hemoglobin and interferes with the ability of the blood to carry oxygen. For this reason, methemoglobinemia is referred to as "blue baby" disease. The EPA limits the concentration of nitrate in public drinking water supplies to 10 mg/L. The standard has been lowered from a previous level of 45 mg/L set by the US Public Health Service and the World Health Organization. TREATMENT: due to its solubility in water and negative ionic charge, filtration and other common home water treatment systems such as softening, or iron filtration does not readily remove nitrate. The best method for limiting nitrate in well water is source control. This can include avoiding overdosing of fertilizer near the well and maintaining good separation distances between septic tank leach fields and the well. A special anion exchange filter that contains a media with a strong affinity for negatively charged ions in water, or by a reverse osmosis treatment system or distillation can remove nitrate. TESTING: Nitrate analysis is usually done by one of the several "wet chemical" methods using a spectrophotometer to read the final color endpoint. Specific ion electrodes also can be used to detect the activity of nitrate in water. This laboratory uses several different wet chemical methods approved under the public water supply laboratory certification program. They also have test kits available, which the laboratory uses to perform an inexpensive "screening test", and with which the homeowner can monitor the change in nitrate levels from their well. They recommend comparing the test kit results against a certified analysis from the lab occasionally to verify the accuracy of the kit. We recommend using a specially prepared bottle that has been rinsed in hydrochloric acid for collecting samples. ,n Ma�hrig Address P O Box 196650 *Anchorage, Alaska 99519 6650 *www muni org Municipality of Anchorage 84i • .� Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 Elmore Road P.O. Box 196650 Anchorage, AK 99507 www.muni.org/onsite (907) 343-7904 AUG AL CERTIFICATE OF ON-SITE SYSTEMS APPROVAL Rm.8 FOR A SINGLE FAMILY DWELLING ((�^ Parcel 1,13. 017-101-22 COSA # O S � 12 i `?�5 K0 Expiration Date: Q —/2- 1. -/21. GENERAL INFORMATION Complete legal description ILIAMNA ACRES TRACT 4A Location (site address) 5400 E. 142ND AVE., ANCHORAGE, AK 99516 Current Property owner(s) DON BENDER Day phone 345-6197 Mailing address ; " PMB 321, 1120 HUFFMAN, ANCHORAGE, AK 99515 Lending agency Day phone Mailing address Real Estate Agent Day phone Mailing Address Unless otherwise requested, COSA will be held by DSD for pickup. 2. NUMBER OF BEDROOMS: 3 3. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well Individual On-site (] Individual Water Storage ❑ Individual Holding Tank ❑ Community Class Well ❑ Community On-site ❑ Public Water System ❑ Public Sewer ❑ The Municipality of Anchorage Development Services Department (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 4 by an independent professional civil engineer registered in the State of Alaska. Certificates of On -Site Systems Approval are required for the transfer of title (except between spouses) for properties served by a single-family on-site wastewater disposal and/or water supply system. DSD also issues COSAs upon request to, homeowners. Certificates of On -Site Systems Approval are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued with new water sample results. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a .public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Spurkland Enginneering Address 203 W. 15th Ave., Ste 202, Anchorage, AK 99501 Engineers Printed Name Lars Spurkland 5. DSD SIGNATURE _Z Approved for bedrooms. Disapproved. Conditional approval for bedrooms, Phone 279-3916 Date AUGUST 9, 2012 OF A<gS�ir' 00 ' 49v yi ....ls. .. . PURKLAND;•� 11 00 with the following stipulations: Attachments: COSA Checklist X Septic System Advisory Well Flow Advisory Nitrate Advisory Arsenic Advisory Maintenance Agreements Supplemental Engineer's Report Other By: _ r G G—C Original Certificate Date: (Rev. 11105) Municipality of Anchorage • Development Services Department Building Safety Division On-Site Water & Wastewater Program ` 4700 Elmore Road P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907)343-7904 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL CHECKLIST Legal Description: ILIAMNA ACRES TRACT 4A Parcel ID: 017-101-22 A. WELL DATA Well type PRI If A, B, or C provide PWSID # — Well Log (Y/N) NO Date completed Sanitary seal (YIN) Y Wires properly protected (Y/N) Y Total depth 98 ft. Cased to >40 ft. Casing height (above ground) 12+ in. FROM WELL LOG AT INSPECTION Date of test UNKNOWN 7/17/2012 Static water level UNKNOWN ft 24 ft Well production UNKNOWN 9-P.M. 5.3 g p m WATER SAMPLE RESULTS: Coliform NEG colonies/100 mL Nitrate 4.76 // mg/L Collected by: SPURKLAND ENG. Arsenic: ND ug/L date of sample: 8/11/ -2 B. SEPTICIHOLDING TANK DATA Tank Type/Material CONCRETE & STEEL Date installed 0/14/70 & 9/13179 Tank size 1 000 gal. Number of Compartments 1/2 Cleanouts (YIN) Y Foundation cleanout (Y/N) Y Depression over tank (Y/N) N High water alarm (Y/N) Y Date of pumping 7/27/12 Pumper ISAAC'S PUMPING SERVICE C. ABSORPTION FIELD DATA Date installed 9/13/79 Soil rating (g.p.d./ft2 or ftz/bdrm) 155 System type SHALLOW TRENCH Length 85 ft. Width 5 ft. Gravel below pipe 4 ft. Total depth 4 ft. Eff. absorption area 465 ft2 Monitoring tube Y Depression over field N Date of adequacy test 7/17/12 Results (PassiFail) PASS For 3 bedrooms Fluid depth in absorption field before test 33 in. Water added 450 gal. New depth50 in. Elapsed Time: 30 min. Final fluid depth 50 in. Absorption rate >= 450 g p d Any rejuvenation treatment (past 12 mo.) (Y/N & type) NO If yes, give date a D. LIFT STATION Date installed "Pump on" level at — Datum Size in gallons in. "Pump off' level at—in. E. SEPARATION DISTANCES Cycles tested --- SEPARATION SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tank/lift station on lot 100'+ Absorption field on lot 100,+ Public sewer main NA Sewer /septic service line 25'+ Animal containment areas 50+ Manhole/Access (Y/N)- High water alarm level at --- Meets Meets alarm & circuit requirements? On adjacent lots 100,+ On adjacent lots 100 + Public sewer manhole/cleanout NA Holding tank NA Manure/animal excrete storage areas 100+ SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation 5+ Property line 5+ Absorption fiield5-+ Water main NA Water service line 10+ Surface water 1001+ Wells on adjacent lots 100,+ SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line 10+ Building foundation 10+ Water main NA Water Service line 10,+ Surface water 100,+ Driveway, parking/vehicle storage 25—+ Curtain drain 50+ Wells on adjacent lots 100'+ F. COMMENTS TRENCH MONITOR/ SUMP BLOCKED 30" ABOVE BOTTOM OF FIELD G. ENGINEER'S CERTIFICATION / .P�E OF ,A�q` 1 certify that t have determined through field inspections and ; 4 H 9 review of Municipal records that the above systems are in :... ... .. .....%.. conformance with MOA COSA guidelines in effect on this date. 00 LARS SPURKLAND SPURK4AND Engineer's Printed Name �� 1 U , Date 8/812012g�� r COSA Fee $ 00 Date of Payment 6 r3I ( a Receipt Number. N L ��% (Rev. 4/10) Waiver Fee $ Date of Payment Receipt Number ral CS1 0i Lwu- - - - - - - - - - - - - - - -- - - - - S i 10' Ilya ESur N 0' 06'00"W r sn�Il�Es�-------X00$3'— -------- I I g CJC mx--iamN iJ I crni»y�m��A�C I� zc>Scn- � I I o�rnc= I I c ymCA c I P I o�aoj P ymiNC Nr�yzn �n-�I zOSZANr-n2 I I CS1 0i Lwu- - - - - - - - - - - - - - - -- - - - - S i 10' Ilya ESur N 0' 06'00"W r sn�Il�Es�-------X00$3'— -------- I I g I a O V E I I I I I � I I CEJ I I N 90 V 5� CJ+ � c.+ N Z OSN mO NO�-I fTI� N.-mO N OZ7 Zl� N N C m r mil 00 '-� oa f*l � CDn -G N F1 C M -i C)Z O5 C-=im I O I M:n u �O VDiD ND mC> O W 50O fin' m X Sm D N➢ZE a C=N C CDn U5 CT) N CD rEi O --< rC<OC O xC�~Af�TI czi Zp� O�(n�� co vCp�cmi�cn O oT �z=r -+<Dcnc OC5 DNZO - EDD O n OJ�Z C ~ =-< M m GJ O n m _ m Cn ➢ fTl p (n O \ C z `C M C)oCDS -'gym o I <D C->C� r W y CO Z Z =Z DO rte= � N z O D m O r;;, O m p_ -o a a oHm c -a vz A �a D � Oo.Z7 0 0 C C oom� w 70m� O~� co � m C'" n a S Z V O m C z w N z C = 0p p �W� Z O G mZ7 C7 O Z-,5 HOZ _ Cn E�EE aj W NO NO CJC mx--iamN iJ I crni»y�m��A�C ooaz�� -imN 00. 0 O% n% oArnno �m�+ioZ I o �z�o��sczn� IQ m S- zmn Amm-y cn -��czWoomf- P p ymiNC Nr�yzn �n-�I zOSZANr-n2 I zc��Arni i I I a O V E I I I I I � I I CEJ I I N 90 V 5� CJ+ � c.+ N Z OSN mO NO�-I fTI� N.-mO N OZ7 Zl� N N C m r mil 00 '-� oa f*l � CDn -G N F1 C M -i C)Z O5 C-=im I O I M:n u �O VDiD ND mC> O W 50O fin' m X Sm D N➢ZE a C=N C CDn U5 CT) N CD rEi O --< rC<OC O xC�~Af�TI czi Zp� O�(n�� co vCp�cmi�cn O oT �z=r -+<Dcnc OC5 DNZO - EDD O n OJ�Z C ~ =-< M m GJ O n m _ m Cn ➢ fTl p (n O \ C z `C M C)oCDS -'gym o I <D C->C� r W y CO Z Z =Z DO rte= � N z O D m O r;;, O m p_ -o a a oHm c -a vz A �a D � Oo.Z7 0 0 C C oom� w 70m� O~� co � m C'" n a S Z V O m C z w N z C = 0p p �W� Z O G mZ7 C7 O Z-,5 HOZ _ Cn E�EE aj W NO NO 00. 0 O% n% ,� yo _a _i o G d , AAROW PUMP Cit WEII SERVICE, LLC WOKE P.O. Box 110496 NO. 9�� Anchorage, AK 99511 Office: (907) 346-9355 • Fax (907) 333-8976 Eagle River: (907) 622-9335 Y` I CUSTOMER ! F JOB SITE. /--%4 r 5 _t L J INVOICE PATE ,WELLDEPTH eWl_ n ^ -0HLORIN70 PUMP DEPTH/ SALESPERSON - 9U Iry DESCRIPTION - `. PRICE -. AMOUNT C 1753- - ? i; I I:g /� .t tyi ,1z i FJ �7 - - f 11 .✓ 7 -:.r r ' e i' z r?z, i ��e+ [[ f LABOR HOURS RATE AMOUNT TOTAL MATERIAL TOTAL LABOR - - i WORK ORDERED BY DATE COMP.TOTAL LABOR PAY THIS AMOUNT X Thank You SIGNATURE (1 Hereby Acknowledge the Satisfactory Completion of the Above Described Work and agree that it above work is not paid for in 90 days I agree to allow Aarow Pump & Weil Service, LLC. the right to remove unpaid for equipment and charge for labor already performed & labor to remove unpaid for equipment.) TERMS: ACCOUNTS PAYABLE AT 10TH OF MONTH FOLLOWING PURCHASE. SERVICE CHARGE AT RATE OF 1.6% PER MONTH WILL BE CHARGED ON OVERDUE ACCOUNTS.