On -Site Water & Wastewater System Permit
Permit Number: OSP241028
Work Type: WellSeptic Renewal
Tax Code Number: 01514177000
Site Legal Address: MOSSFLOWERWOODS LT 4 G:2636
Site Mailing Address: 11145 FIRESIDE CIR, Anchorage
Owner: NOBLETT PATRICK
Design Engineer: FORGE ENGINEERING
This permit is for the construction of:
Effective Date:
Expiration Date:
pent S
_c
w n
Dehartnnent
Lot Size in Sq Ft
Total Bedrooms:
3/5/2024
3/5/2025
43641
Q Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well 0 Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
Special Provisions:
• The Record Drawing is to show the stormwater line.
i
9eEeived-By: 55 e� -ho fOr e- /1 Date:
Issued By: GjU Date: Z4-1
4
MUNICIPALITY OF ANCHORAGE
0 -'...�
Community Development Department -- Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 015-141-77
Property owner(s) Patrick Noblett
Mailing address 10618 Ketch Circle, Anchorage AK 99516
Site address 11145 Fireside Circle
Day phone (907) 529-7702
Legal description (Sub'd., Block & Lot) Mossflower Woods, Lot 4
Legal description (Township, Range & Section)
Lot Size 43,641 Sq. Ft. Number of Bedrooms 4
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
(M all that apply)
Absorption Field
❑X
Initial ®
Single Family (SF) ❑X
Septic Tank
❑X
Upgrade f-1(w/wo
ADU)
Holding Tank
ElRenewal
N1
Duplex (D) ❑
El
Multiple
Multiple Dwellings ElPrivy
and/or D)
Private Well
❑X
Water Storage
❑
THIS APPLICATION
INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
oci � i
(Signature of property owner or authorized agent)
Permit/Rush Fees: 12--; Z Waiver Fees:
Date of Payment:
Receipt Number:
Permit No.
Permit App_:;- : , �. c
Date of Payment:
Receipt Number:
Waiver No.
March 4, 2024
MOA Development Services, On-Site Water & Wastewater Program
4700 Elmore Rd
Anchorage, AK 99507
Subject: Mossflower Woods Lot 4
Septic System Permit Renewal
Dear On-Site Services Engineer:
The permit for the construction of a well and septic system on Lot 4, Mossflower Woods Sub, has
expired. A site visit was conducted and there have been no substantial changes to this lot or to the
surrounding area since the permit was originally issued. The current design and permit conditions
meet all code requirements. The proposed well location also meets the 100’ separation distance
to the stormwater line on E 112th. We therefore request the renewal of the permit for the well and
septic system on this lot.
Sincerely,
Benjamin Schiller, PE
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP241028, Deb Wockenfuss, 03/05/24
MUNICIPALITY OF ANCHORAGE
On -Site Water & Wastewater Program
PO Box 196650 4700 Elmore Road
Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997
http://www.muni.org/onsite
On -Site Water & Wastewater System Permit
Permit Number: OSP221355
Work Type: WellSeptic Initial
Tax Code Number: 01514177000
Site Legal Address: MOSSFLOWERWOODS LT 4 G:2636
Site Mailing Address:
Owner: NOBLETT PATRICK
Design Engineer: FORGE ENGINEERING
This permit is for the construction of:
Effective Date
Expiration Date:
Lot Size in Sq Ft:
Total Bedrooms:
�o�l»cnr
�S f
Department
9/23/2022
9/23/2023
43641
Q Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy Q Private Well ❑ Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
Received By:
Issued By:
Date:
Date: 9h 3/?'
4
MUNICIPALITY OF ANCHORAGE
o�
Community Development Department "' Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 015-141-77
Property owner(s) Patrick Noblett
Mailing address 10618 Ketch Circle, Anchorage AK 99516
Site address NHN Fireside Circle
Day phone
Legal description (Sub'd., Block & Lot) Mossflower Woods, Lot 4
Legal description (Township, Range & Section)
Lot Size 43,641 Sq. Ft. Number of Bedrooms 4
APPLICATION IS FOR: APPLICATION IS AN:
TYPE OF DWELLING:
(® all that apply)
Absorption Field ❑X Initial 0
Single Family (SF) ❑X
(w/wo ADU)
Septic Tank 1ZUpgrade ElDuplex
(D) F-1Holding
Tank ElRenewal El
Multiple Dwellings ❑
Privy ❑
(SF and/or D)
Private Well ❑X
Water Storage ❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that
this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees: � 996,
Date of Payment: '?/7/gA
Receipt Number: 0111M ID
Permit No. Al I? a a l 35S
Permit App__- : ,..mac
Waiver Fees:
Date of Payment:
Receipt Number:
Waiver No.
September 6, 2022
MOA Development Services, On-Site Water & Wastewater Program
4700 Elmore Rd
Anchorage, AK 99507
Subject: Mossflower Woods, Lot 4
Septic system design
Dear On-Site Services Engineer:
The owner of the above lot intends to build a 4-bedroom home on the property, so we are
submitting this permit application for the construction of a new well and septic system. The
attached site plan identifies the location of the home as well as the proposed well, septic location
and alternate site. No conflicts exist between this proposed system and any other well or septic
system, whether on this lot or adjacent lots.
The ground surface on the lot slopes moderately toward the road. There are no slopes greater than
25% within 50 feet downslope of either the primary or alternate site. Contours are shown on the
site plan showing the grade and direction of flow. Stormwater drainage will not impact this septic
system. The new trench will be constructed parallel to the slope as much as possible.
Wells on this and adjacent lots are shown. The new system will be a minimum of 100’ from all
wells and surface water, and more than 5’ away from the septic tank. The alternate site is located
more than 10’ away.
There is one test hole on the lot with a soils log, percolation testing, and groundwater monitoring.
In addition, we are submitting additional test holes from neighboring lots and from the
geotechnical report in the road. All demonstrate no impermeable layers down to more than 16’ and
no groundwater developing at any point. We request that this additional test hole information be
accepted to demonstrate adequate separation to groundwater and to impermeable layers.
Please refer to the attached test hole logs, soils lab analysis, plan and profile pages for the septic
design. If this design is followed, there will be no adverse impacts to adjacent properties.
Sincerely,
Benjamin Schiller, PE
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP221355, Deb Wockenfuss, 09/23/22
ALTERNATE SITE
MIN 8' SEPARATION
Benjamin Schiller
CE 12592R
EGISTEREDPROFES S I O N ALENGINEER
1"=50'
50' LONG x 5' WIDE, 4' EFFECTIVE
DEPTH ABSORPTION TRENCH
1250-GAL SEPTIC TANK
w/ 20" MANWAY
CO - CLEANOUT
2CO - DOUBLE CLEANOUT
FCO - FOUNDATION CLEANOUT
FS - FLOW SPLITTER VALVE
MH - MANHOLE
MT - MONITORING TUBE
SV - SEPTIC VENT
TH - TEST HOLE
LEGEND
TH#4A
MOSSFLOWER WOODS, LOT 4
FEET
0 50 100
FCO
NOTE:
NO SLOPES >25% WITHIN 50' OR SURFACE WATER WITHIN 100' OF THE
PROPOSED SEPTIC SYSTEM
ALL WELLS ON SURROUNDING LOTS WITH IMPACTS TO THIS
PROPERTY ARE SHOWN. NO CONFLICTS WITH WELLS OR SEPTIC
SYSTEMS.FIRESIDE CIRCLE4-BDRM
HOME10' T&E EASEMENT
E. 112th AVENUE
400
405
410
415
420
2CO
CO
CO
PROPOSED WELL WITH
100' RADIUS
MT
MT
WELL RADII FROM LOTS 2&3
WELLS ARE OFF PAGE. SEE NOTE
AT BOTTOM OF THIS SHEET
NEIGHBORING LOT
WELL RADII
NEIGHBORING
SEPTIC SYSTEM
9/20/22
≥10'
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP221355, Deb Wockenfuss, 09/23/22
MOSSFLOWER WOODS, LOT 4
TYPICAL TRENCH SECTION
(NO SCALE)
NOTES:
1. GRADE AREA OVER TRENCH TO DRAIN AWAY
2. PROVIDE 3' OF COVER OVER TRENCHES AND 4' OVER SEPTIC TANK, OR 2'
WITH 2" OF INSULATION
3. CHECK GROUNDWATER AT TIME OF CONSTRUCTION. IF LEVEL IS HIGHER
THAN PREVIOUSLY OBSERVED, CALL ENGINEER IMMEDIATELY
Benjamin Schiller
CE 12592R
EGISTEREDPROFES S I O N ALENGINEERSep 06, 2022
4" PERFORATED PVC
(HOLES DOWN)
DRAINFIELD ROCK
5'
6"
3'
4'
DESIGN FACTORS:SYSTEM REQUIREMENTS:
600 GPD PEAK FLOW
PERK RATE: <1 MIN/IN
APPLICATION RATE: 1.2 GPD/SF
5' WIDE TRENCH SYSTEM
1,250-GAL SEPTIC TANK
BOTTOM OF TRENCH: 7' BELOW GRADE
FLOW LINE ELEVATION: 3' BELOW GRADE
TOP OF TRENCH: 0.5' ABOVE GRADE
600 GPD / 1.2 GPD/SF / 5-WIDE * 0.5 RED (4' DEEP) = 50 LF TRENCH REQUIRED (50 LF SPECIFIED)
GEOTEXTILE FABRIC
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP221355, Deb Wockenfuss, 09/23/22
Municipality of Anchorage
Development Services Department
On -Site Water and Wastewater Section
4U*j700 Elmore St.
P.O. Box 196650 Anchorage, AK 99519-6650
www.muni.org/onsite
(907)343-7904
Soils Log - Percolation Test
Performed For: LAND LCC
Legal Description: MOSSFLOWER WOODS, LOT 4
1-
2-
3-
4-
5-
6-
7-
8-
9-
10-
11-
12-
13-
14-
15-
16-
17-
18-
19-
20 -
�u .E 09ap'N"C5 (0�
S11.N SAO (5M)
&AVIF, w1 5A�D
5 Stli CSP- C-tM�
C'IkP*L Ftp ;D 3"
50µi CoB>;+O
Date Performed:
Township, Range, Section:
WAS GROUND WATER
ENCOUNTERED? NO
s
30vk IF YES, AT WHAT DEPTH? L
Depth to Water After P
Monitoring? NGWE E
Date: 10-19-20 I I 1
/0/10 /2-0 AJ,,i,
OF A4 -\A4
Z. v
NTYl'. ' THEWS •
CE 135444
FE 10
10-17-20
Site Plan
SEE ATTACHED SITE PLAN
Reading
Date
Gross Time
Net Time
Depth to Water
Net Drop
10-17-20
---
0 MIN
50"
---
5 MIN
5 MIN
52.25"
2.25"
5 MIN
10 MIN
56.5"
6,5°
5 MIN
15 MIN
59.5"
9.5"
PERCOLATION RATE 2 (minutestinch) PERC HOLE DIAMETER 6"
TEST RUN BETWEEN 4 FT AND 5 FT
COMMENTS HOLE WAS PRESOAKED PRIO TO TESTING. PERC READINGS ARE WITHIN 1/4"
PERFORMED BY: TRIAD ENGINEERING, LLC I GRANT MATHEWS, PE CERTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 10-19-20
Depth
(Feet)
1-
2-
3-
4-
5-
6-
7-
8-
9-
10-
11-
12-
13-
14-
19-
20-
FT AND FT
I
(ENGINEER'S SEAL)
Performed For:
Legal Description:
15-
16-
PERC HOLE DIAMETER
Date Gross Time
Slope Site Plan
PERCOLATION RATE (minutes/inch)
Net Time Depth to Water Net DropReading
COMMENTS
TEST RUN BETWEEN
17-
18-
PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE:
CERTIFY THAT THIS TEST WASPERFORMED BY:
(907)343-7904
Soils Log - Percolation Test
Township, Range, Section:
WAS GROUND WATER
ENCOUNTERED?
IF YES, AT WHAT DEPTH?
S
L
O
P
E
Date:
Depth to Water After
Monitoring?
Date Performed:
Municipality of Anchorage
Development Services Department
On-Site Water and Wastewater Section
4700 Elmore St.
P.O. Box 196650 Anchorage, AK 99519-6650
www.muni.org/onsite
8-14-22
Mossflower Woods, Lot 4
Patrick Noblett
See attached site plan
No
NGWE
8-30-22
6.000"
0.000" 6.000"2 min
6.000"
2 min 4 min 0.000"
2 min
6.000"
6.000"
2 min 6 min 0.000" 6.000"
Added 2 gallons of water in less than 1 minute. All water absorbed in less than 2 minutes. Repeated test multiple times with same
results. Material is predominantly sand (visual classification). A sand liner should not be required.
Triad Engineering, LLC Grant Mathews
14:11
14:13
14:15
14:17
1
2
3
---- ---- ----
----
--------
---- ----
----
6"
4.5 5.5
<1
8-30-22
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP221355, Deb Wockenfuss, 09/23/22
% GRAVEL 27.8 USCS SW-SM
% SAND 65.4 USACOE FC N/A
% SILT/CLAY 6.8 % PASS. 0.02 mm N/A
% MOIST. CONTENT 6.2 % PASS. 0.002 mm N/A
N/A
N/A
N/A
SIEVE SIEVE TOTAL %SPECIFICATION
SIZE (mm)SIZE (U.S.)PASSING (% PASSING)
152.40 6"
76.20 3"100
38.10 1.5"95
19.00 3/4"83
12.70 1/2"79
9.50 3/8"76
4.75 #4 72
2.00 #10 67
0.85 #20 55
0.43 #40 29
0.25 #60 16
0.15 #100 10
0.075 #200 6.8
ELAPSED DIAMETER
TIME (MIN) (mm)
0
1
2
5
8
15
30
60
250
1440
SOUNDNESS OF AGG.
(ASTM C88)
DEGRADATION
(ATM T-313)
LA ABRASION
(ASTM C131/C535)
SP. GRAV. COARSE AGG.
(ASTM C127)
11301 Olive Lane ∙ Anchorage, Alaska 99515 ∙ Phone: 907-344-5934 ∙ Fax: 907-344-5993 ∙ www.nge-tft.com
N/A
N/A
The testing services reported herein have been performed to recognized industry standards, unless otherwise noted. No other warranty is made. Should engineering
interpretation or opinion be required, NGE-TFT will provide upon written request.
N/A
HYDROMETER RESULT
N/A
SIEVE ANALYSIS RESULT
2022 Materials Testing
6309-22
Mossflower Woods Lot 4
22-S-6
Well-graded sand w/ silt and gravel
8/26/2022
Erik Boatwright
Andrew Fortt
TOTAL %
PASSING
9.1
1.0
Forge Engineering, Inc.PROJECT CLIENT:
PROJECT NAME:
PROJECT NO.:
SAMPLE DESC.:
NGE-TFT ID #:
CLASSIFICATION:
DATE RECEIVED:
TESTED BY:
REVIEWED BY:
UNIFORMITY COEFFICIENT (Cu)
COEFFICIENT OF GRADATION (Cc)
ASTM D1557 (uncorrected)
ASTM D4718 (corrected)
OPTIMUM MOIST. CONTENT. (corrected)
115
120
125
130
135
140
145
0 2 4 6 8 10 12 14 16DRY DENSITY (pcf)MOISTURE CONTENT (%)
MOISTURE-DENSITY RELATIONSHIP ASTM D1557
SILT or CLAYCOBBLES
GRAVEL
Coarse Fine
SAND
Coarse Medium Fine
0
10
20
30
40
50
60
70
80
90
100
0.0010.010.1110100FINER BY MASS (%)GRAIN SIZE (mm)
PARTICLE SIZE ANALYSIS ASTM D6913 / C136 / D422
#200#40#101.5 1/2363/4 #4 #20 #60 #1003/8
U.S.SIEVE OPENING IN INCHES U.S.SIEVE NUMBERS HYDROMETER